Browse content of UTPedia using Year, Subject, Department and Author and Search for required document using Searching facilities included in UTPedia. UTPedia with full text are accessible for all registered users, whereas only the physical information and metadata can be retrieved by public users. UTPedia collaborating and connecting peoples with university’s intellectual works from anywhere.

Disclaimer - Universiti Teknologi PETRONAS shall not be liable for any loss or damage caused by the usage of any information obtained from this web site.Best viewed using Mozilla Firefox 3 or IE 7 with resolution 1024 x 768.

THE STUDY OF SAFETY DISTANCE BETWEEN TOWER AND SATELLITE DISH FOR LIGHTNING PROTECTION SCHEME USING ROLLING SPHERE METHOD

AHMAD DAUD, MOHAMAD AKHMAL BIN (2012) THE STUDY OF SAFETY DISTANCE BETWEEN TOWER AND SATELLITE DISH FOR LIGHTNING PROTECTION SCHEME USING ROLLING SPHERE METHOD. Universiti Teknologi PETRONAS.

[img]
Preview
PDF
Download (1792Kb) | Preview

Abstract

The development of a computer program for the evaluation of lightning safety distance between the tower and satellite dish is written in M-File MATLAB simulation software. The 3-Dimensional illustrative graphics model is used in order to have better understanding on how lightning protection system (LPS) works. The study of physical length of grounding electrode use on the tower is found to be significantly affecting the grounding system performances. The performances of grounding system are depending on magnitude of lightning strikes current being dispersed and the settling time for lightning strikes current is completely dispersed. The grounding system performances is studied by using lightning current impulse (LCI) generator, simulated in OrCad PSpice simulation software. It is found that the optimum length of vertical lightning rod in LPS should be the same with the striking distance. There is no significant improvement is found in lightning safety distance if the length of vertical lightning rod is higher than striking distance. The lightning strikes peak current that have larger magnitude than the withstand insulation level of specified object should cause no physical damage. It is because the lightning safety distance will also increase whenever the lightning strikes peak current become bigger. It is also found that the lower grounding impedance will produce higher magnitude of dispersed peak current and faster settling time.

Item Type: Final Year Project
Subject: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Engineering > Electrical and Electronic
Depositing User: Users 1278 not found.
Date Deposited: 02 Oct 2012 16:02
Last Modified: 25 Jan 2017 09:40
URI: http://utpedia.utp.edu.my/id/eprint/3761