Browse content of UTPedia using Year, Subject, Department and Author and Search for required document using Searching facilities included in UTPedia. UTPedia with full text are accessible for all registered users, whereas only the physical information and metadata can be retrieved by public users. UTPedia collaborating and connecting peoples with university’s intellectual works from anywhere.

Disclaimer - Universiti Teknologi PETRONAS shall not be liable for any loss or damage caused by the usage of any information obtained from this web site.Best viewed using Mozilla Firefox 3 or IE 7 with resolution 1024 x 768.

ELECTRICAL OVERCURRENT PROTECTION GRADING IN V4D

Engonga Ela Akaba, Miguel Angel (2015) ELECTRICAL OVERCURRENT PROTECTION GRADING IN V4D. IRC, Universiti Teknologi PETRONAS. (Submitted)

[img] PDF
Download (1337Kb)

Abstract

Selective Coordination contributes to the localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the choice of overcurrent protective devices and their ratings and settings. Selective Coordination is critical for the reliability of electrical distribution system and must be analyzed and test regularly. A properly engineered and installed system will allow only the nearest upstream overcurrent protective device to open for both overload and all types of short-circuits, leaving the remainder of the systems undisturbed and preserving continuity of service. The aim of this study is to perform a Coordination and Overload study for the electrical installation in Village-4D T1, in order to know the root causes of the continuous tripping of its main Circuit Breaker which results in frequent power outage in the area. The revision of past researches was the first step taken toward understanding the concept involving protections; followed by a series of site inspections which helped gather the relevant data needed for the study such as the types of protective devices and their arrangement as well as the ratings. The methodology required a sensitivity analysis of the CBs in the area of study and Overload study in which fault levels were simulated using Simulink/MATLAB. The preliminary results of the study based on CBs level of sensitivity showed that V4D protective devices level of sensitivity is medium, therefore less prone to nuisance tripping outside the nominal tripping current. Thus sensitivity is not the factor causing the breaker to trip. However the results from the overload study show that the increasing number of overheating appliances used by students causes the circuit to overload, thus tripping the main breaker.

Item Type: Final Year Project
Academic Subject : Academic Department - Electrical And Electronics - Pervasisve Systems - Digital Electronics - Design
Subject: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Engineering > Electrical and Electronic
Depositing User: Ahmad Suhairi Mohamed Lazim
Date Deposited: 31 May 2016 16:29
Last Modified: 25 Jan 2017 09:34
URI: http://utpedia.utp.edu.my/id/eprint/16623

Actions (login required)

View Item View Item

Document Downloads

More statistics for this item...