PART LOAD PERFORMANCE ANALYSIS OF ELECTRIC CHILLER AND STEAM ABSORPTION CHILLER AT DISTRICT COOLING PLANT

ZULAZNI, MUHAMMAD ASYRAF (2017) PART LOAD PERFORMANCE ANALYSIS OF ELECTRIC CHILLER AND STEAM ABSORPTION CHILLER AT DISTRICT COOLING PLANT. [Final Year Project]

[thumbnail of FYP 2 Dissertation (Muhammad Asyraf Bin Zulazni, 20024, ME).pdf] PDF
FYP 2 Dissertation (Muhammad Asyraf Bin Zulazni, 20024, ME).pdf
Restricted to Registered users only

Download (1MB)

Abstract

Universiti Teknologi PETRONAS (UTP) uses district cooling (DC) system for air-conditioning purpose. The UTP GDC plant produces chilled water. Chilled water is produced by two different types of chillers namely the Electric Chiller (EC) and Steam Absorption Chiller (SAC). This study investigated the performance of both EC and SAC by evaluating Coefficient of Performance method (COP) under theoretical and actual operating conditions. Microsoft Excel spreadsheet software was used to evaluate the COP. Historical data from UTP GDC from January 2016 to March 2016 were used for analysis. Evaluated COP for the electric chiller varies from 3.12 to 7.11 while the evaluated COP for steam absorption chiller varies from 1.07 to 1.31.

Item Type: Final Year Project
Subjects: T Technology > TJ Mechanical engineering and machinery
Departments / MOR / COE: Engineering > Mechanical
Depositing User: Mr Ahmad Suhairi Mohamed Lazim
Date Deposited: 01 Aug 2018 09:53
Last Modified: 01 Aug 2018 09:53
URI: http://utpedia.utp.edu.my/id/eprint/17947