The report presents the study on the Thermal Storage tank charging system for Thermal Energy Storage (TES) System of UTP. The system supplies chilled water to UTP at 6oC while the return chilled water is at 13.5oC.The chilled water from steam absorption chiller (SAC) is supplied directly to UTP which only operated during the day. Chilled water from TES tank is charged by electric chillers and is used as supplementary for meeting cooling load demand during peak requirements. The current practice is to operate at night to charge the TES tank. Due to the time limitations, full charging of thermal storage tank could not be achieved.